Non-slime
The non-slime series is a water treatment agent developed by our company that prevents the occurrence and growth of harmful microorganisms in the cooling water system that have caused trouble in recent years.
Features
Effective against a wide range of bacteria, filamentous fungi, yeasts and algae.
It also acts strongly against Legionella bacteria and has antibacterial and antibacterial effects.
It is non-oxidizing and does not corrode metals.
Since it does not contain heavy metals, it is not regulated by wastewater standards.
Removes slime obstacles and prevents deterioration of thermal efficiency.
Can be combined with anti-corrosion agents and scale inhibitors.
Perlin Water Purifying Compound
Prevents scaling and corrosion of closed and open cooling water and hot water.
MP/CP Series Features
Forms a coating with a special polymer to completely prevent corrosion.
The action of the special polymer makes the calcium component into fine particles to prevent scale.
If there is existing scale, it prevents the growth of crystals such as calcium and gradually exfoliates it.
Not only does heat loss due to scale adhesion disappear, but iron rust inside the pipe due to corrosion also disappears.
HP/UP Series Features
A hygienically safe rust preventive that uses a product that has passed food additive standards.
Prevents corrosion of metals by forming an antirust phosphate film and sequestering metal ions.
It almost eliminates iron rust inside the pipes due to corrosion, etc., and prevents the occurrence of red water.
MH/CH Series Features
MH and CH types have anti-scaling and anti-corrosion properties of conventional MP and CP types, as well as non-slime anti-algae and sterilization effects.
It is a one-liquid type and easy to handle.
HC12 Series Features
A sanitizer containing sodium hypochlorite as the main ingredient.
Asa-Clean
Features
Because it is crystal-like and very hard, it dissolves only gradually in water, so there is no inconvenience of dissolving and pouring, and it is very easy to manage.
Prevents the harm of sulfurous acid gas caused by air pollution.
Stops the generation of rust in piping and removes scale.
Sequesters metal ions such as iron in water.
The red water will be clear in 2-3 days after use.
Water with Asa-Clean is tasteless, odorless and harmless.
It can also be used for drinking water because it uses food additive standard products.
Perlin Water Purifying Compound Management Criteria (Standard) | hot and cold water |
PH | 6.5 to 8.5 |
Electrical conductivity (mS/m) | 80 or less |
chloride ion (Cl-mg/l) | 200 or less |
M alkalinity (mg/l) | 100 or less |
Total hardness (mg/l as CaCO3) | 200 or less |
Silica (SiO2 mg/l) | 100 or less |
List of water purification agents
Non-slime
Product number/Main ingredient | Bacteria | Algae | Fungus | Legionella | Scale | corrosion | Cooling water | Warm water | Drinking water |
K100/nitrogen sulfur | ○ | ○ | ○ | ○ | ○ | ||||
W100/isothiazoline | ○ | ○ | ○ | ○ | ○ | ○ | |||
N100/Hydrazine hydrate | ○ | ○ | ○ | ○ | ○ | ○ | ○ | ||
H100/Chlorine dioxide | ○ | ○ | ○ | ○ | ○ | ||||
AG100/Silver ion | ○ | ○ | ○ | ○ | ○ | ○ | |||
B300 (tablet form) / bromine, chlordimethyl, hydantoin | ○ | ○ | ○ | ○ | ○ |
Perlin Water Purifying Compound
Product number/Main ingredient | Bacteria | Algae | Fungus | Legionella | Scale | corrosion | Cooling water | Warm water | Drinking water |
MP Series, CP Series / Phosphonic acid, carboxylic acid, polyacrylic acid, maleic acid, etc. | ○ | ○ | ○ | ○ | |||||
HP□ Series, UP□ Series/Phosphate-based | ○ | ○ | ○ | ○ | ○ |
Asa-Clean
Product number/Main ingredient | Bacteria | Algae | Fungus | Legionella | Scale | corrosion | Cooling water | Warm water | Drinking water |
Solid/Phosphate type | ○ | ○ | ○ | ○ |
tower pro
Product number/Main ingredient | Bacteria | Algae | Fungus | Legionella | Scale | corrosion | Cooling water | Warm water | Drinking water |
Solid/carboxylic acid type, triazine type | ○ | ○ | ○ | ○ | ○ | ○ | ○ |
Perlin Water Purifying Compound (multi-purpose treatment agent)
Product number/Main ingredient | Bacteria | Algae | Fungus | Legionella | Scale | corrosion | Cooling water | Warm water | Drinking water |
MH Series, CH Series / Non-Slime + MP CP | ○ | ○ | ○ | ○ | ○ | ○ | ○ | ○ |